Humbert Copper Connect LLC. offers infrared scanning. Thermal Imaging is a valuable tool that can find possible problems with your electrical switchgear.

We can offer these services as a preventative maintenance service, or as an installation verification.

HCC maintains the latest up to date Fluke equipment and software. Used as a diagnostic tool, Thermography allows corrective actions before very costly failures and faults take place. 

Infrared Thermography is the most powerful and cost effective preventative maintenance tool available today!


Prepared for Humbert Copper Connect


Panel_PIP.is2 Visible Light Reference
1/4/2006 10:22:10 AM
It appears the two hot connections may be
overloaded.

Annotations
Location Building 1
Equipment Breaker
Potential Problem Overload
Severity Yellow
Recommended Action Monitor

Markers
Label Temperature Emissivity Background
P0 109.9 °F 0.95 68.0 °F
P1 116.2 °F 0.95 68.0 °F



Main_IR.is2 Visible Light Reference
 1/19/2006 2:59:53 PM
A phase appears to be severly out of balance. 
 
Annotations
Location Building 2
Equipment Capacitor
Potential Problem Overload
Severity Red
Recommended Action Schedule Maintenance
 
Markers
Label  Temperature Emissivity Background
P0 274.8 °F 0.98 68.0 °F
P1 197.5 °F 0.98 68.0 °F
P2 162.5 °F 0.98 68.0 °F


3_Phase_Labeled_PIP.is2 Visible Light Reference
1/19/2006 3:07:32 PM
There is a strong imbalance that may be due to a
blown fuse. Schedule maintenance to inspect the
fuses and load levels.   
   
 Annotations
Location Building 2
Equipment Disconnect
Potential Problem Imbalance
Severity Red
Recommended Action Schedule Maintenance

Markers
Label Average Minimum Maximum Emissivity Background Std. Dev.
B Phase 126.7 °F 96.2 °F 144.3 °F 0.98 68.0 °F  6.028
C Phase 118.5 °F 89.2 °F 137.3 °F 0.98 68.0 °F  7.299
A Phase 104.2 °F   86.6 °F 117.6 °F  0.98 68.0 °F 2.789
 
B2_Panel_Full_Screen.is2 Visible Light Reference
3/31/2006 11:01:34 AM
It appears 2 or 3 connections may be overloaded.
Schedule maintenance to determine load
requirements.
 
 Annotations
Location Building 2
Equipment Breaker
Potential Problem Overload
Severity Red
Recommended Action Schedule Maintenance

Markers
Label Temperature Emissivity Background
P0 128.8 °F 0.95 68.0 °F
P1 138.9 °F 0.95 68.0 °F
P2 146.6 °F 0.95 68.0 °F